Quick answer
A flash point is the lowest temperature at which a solvent gives off enough vapour to ignite near a flame or spark. Low-flash solvents like acetone and MEK can ignite at room temperature, so store them ventilated, away from ignition sources and oxidizers, grounded during transfer, with bulk stock in a dedicated flammables store.
A solvent's flash point is the lowest temperature at which it gives off enough vapour to ignite near an open flame or spark. It's the single number that most determines how a flammable solvent needs to be stored and handled.
Flash points of common solvents
| Solvent | Approx. flash point (closed cup) |
|---|---|
| n-Hexane | −22°C |
| Acetone | −20°C |
| MEK (methyl ethyl ketone) | −9°C |
| Ethyl acetate | −4°C |
| Toluene | 4°C |
| Methanol | 11°C |
| Isopropyl alcohol (IPA) | 12°C |
| Ethanol | 13°C |
| Xylene (mixed) | about 25–30°C |
| n-Butanol | 35°C |
Values are typical literature figures and vary slightly by source and purity. Use the flash point in section 9 of the supplier’s SDS for your own risk assessment. Anything below room temperature can ignite in a normal store.
What Flash Point Actually Tells You
A low flash point means the solvent can form an ignitable vapour-air mixture at or near normal room temperature — acetone, MEK and many of our other light solvents fall in this category. A higher flash point means the liquid has to warm up considerably before vapour ignition becomes a risk, which changes how much ventilation and ignition-source control a given storage area actually needs.
Storage Basics for Flammable Solvents
- Store away from all ignition sources — open flames, sparking equipment, and anything that generates static discharge.
- Keep storage areas ventilated so vapour can't accumulate to a flammable concentration.
- Use grounding/bonding when transferring solvent between containers to prevent static discharge igniting vapour.
- Store in appropriately rated containers and cabinets, separated from oxidizers (see our guide on chemical storage compatibility).
- Keep quantities in the work area to what's needed for the shift — bulk stock belongs in a dedicated flammables store, not the shop floor.
Products Where This Applies Directly
Most of our solvents and organic chemicals carry a flammability hazard to some degree — acetone, toluene, xylene, IPA, ethyl acetate and MEK among them. Check the specific product's SDS for its exact flash point and handling requirements before storing or scaling up use.