Quick answer

A flash point is the lowest temperature at which a solvent gives off enough vapour to ignite near a flame or spark. Low-flash solvents like acetone and MEK can ignite at room temperature, so store them ventilated, away from ignition sources and oxidizers, grounded during transfer, with bulk stock in a dedicated flammables store.

A solvent's flash point is the lowest temperature at which it gives off enough vapour to ignite near an open flame or spark. It's the single number that most determines how a flammable solvent needs to be stored and handled.

Flash points of common solvents

SolventApprox. flash point (closed cup)
n-Hexane−22°C
Acetone−20°C
MEK (methyl ethyl ketone)−9°C
Ethyl acetate−4°C
Toluene4°C
Methanol11°C
Isopropyl alcohol (IPA)12°C
Ethanol13°C
Xylene (mixed)about 25–30°C
n-Butanol35°C

Values are typical literature figures and vary slightly by source and purity. Use the flash point in section 9 of the supplier’s SDS for your own risk assessment. Anything below room temperature can ignite in a normal store.

What Flash Point Actually Tells You

A low flash point means the solvent can form an ignitable vapour-air mixture at or near normal room temperature — acetone, MEK and many of our other light solvents fall in this category. A higher flash point means the liquid has to warm up considerably before vapour ignition becomes a risk, which changes how much ventilation and ignition-source control a given storage area actually needs.

Storage Basics for Flammable Solvents

  • Store away from all ignition sources — open flames, sparking equipment, and anything that generates static discharge.
  • Keep storage areas ventilated so vapour can't accumulate to a flammable concentration.
  • Use grounding/bonding when transferring solvent between containers to prevent static discharge igniting vapour.
  • Store in appropriately rated containers and cabinets, separated from oxidizers (see our guide on chemical storage compatibility).
  • Keep quantities in the work area to what's needed for the shift — bulk stock belongs in a dedicated flammables store, not the shop floor.

Products Where This Applies Directly

Most of our solvents and organic chemicals carry a flammability hazard to some degree — acetone, toluene, xylene, IPA, ethyl acetate and MEK among them. Check the specific product's SDS for its exact flash point and handling requirements before storing or scaling up use.

Request a Quote Talk to Our Team